      Distributed fault location device for transmission lines

      型號:DX-WPS100-GZ01

      Online Inquiry+8618926454155


      Product details

      Distributed fault location and hidden danger monitoring device for transmission lines

      model:DX-WPS100-GZ01

      1、 Demand analysis

      With the increasing number of high-voltage long-distance overhead transmission lines, transmission lines, as the link of energy transmission, are the basis for the safe and stable operation of the whole system; Once a fault occurs on the transmission line, it is necessary to find the fault point as soon as possible, eliminate the fault and restore power supply. However, as high-voltage and ultra-high voltage transmission lines are often exposed to different environments and distributed in a wide geographical area, the operating environment is harsh; Therefore, it is also a place where many faults occur in the power system. It is very important to quickly and accurately find the fault point after the line fault, not only for timely repair of the line and rapid restoration of power supply, but also for the security, stability and economic operation of the entire power system.


      2、 Working principle

      The distributed fault location and hidden danger monitoring device for transmission lines adopts the distributed traveling wave measurement technology. The monitoring terminals are distributed on the transmission line conductors. The power frequency fault signals and traveling wave fault signals near the line fault time point are collected at high potential and sent back to the background data center in 4G/5G wireless ways. Through the comprehensive analysis of the data center, the fault point can be quickly and accurately determined according to different fault characteristics, Improve fault location accuracy to improve fault line patrol efficiency, and also capture transient fault traveling wave waveform to intelligently identify whether the fault is a lightning strike fault or a non lightning strike fault, and whether the lightning strike fault is a shielding strike or a counterattack. The diagnosis results are displayed in two ways: web and SMS, and sent to users, which is helpful to timely repair the fault line and ensure the safe and stable operation of the whole power grid.


      3、 Product Functions

      (1) Basic configuration of fault location monitoring: main control unit, fault location monitoring unit, communication unit, inductive power supply unit, solar power supply unit, mounting bracket and auxiliary materials.

      (2) Detection and calculation of fault distance: it can accurately detect and record the distance of single-phase ground fault, interphase short circuit fault, open circuit fault and instantaneous fault of the line online;

      (3) High precision fault location: it can accurately determine the fault section of transmission line, and the reliability of section location is more than 99%;

      (4) The error is not more than 300 meters: it can accurately determine the fault location of the transmission line, and the location error is 300 meters

      (5) Fault cause identification function: it can identify lightning strike fault and non lightning strike fault, and the accuracy of lightning strike and non lightning strike fault identification is more than 95%;

      (6) High identification accuracy: it can identify shielding failure and counterattack failure, and the identification accuracy of lightning strike fault nature is more than 90%

      (7) Dual RAM recording technology: dual RAM recording technology is adopted to eliminate the "dead zone of recording" of transient signals and prevent the omission of fault data caused by lightning current interference;

      (8) It can record line lightning current, locate lightning strike points and count lightning strike times online;

      (9) It can detect line load current online, including timing return and call to measure load current data;

      (10) The software has the functions of automatic fault identification, output alarm and data file storage;

      (11) 4G/5G wireless transmission: 4G/5G network encryption transmission, measurement;

      (12) Support remote upgrade: support remote parameter setting and program upgrade


      4、 Technical parameters

      Serial No

      category

      project

      technical parameter

      1     

      Overall performance

      Complete machine configuration

      Main control unit, fault location monitoring unit, communication unit, inductive power supply unit, solar power supply unit and installation auxiliary materials.

      2     

      Overall quality

      Less than 15KG

      3     

      texture of material

      Aluminum mold body

      4     

      Fault location monitoring unit

      Fault location sensor

      Interval positioning reliability ≥ 99%; Positioning error ≤ 100m

      5     

      Detect line length

      30km

      6     

      Traveling wave sensor broadband

      1kHz2MHz

      7     

      Traveling wave sampling rate

      5MHz

      8     

      Single conductor fault current measurement range

      10A15000A(Valid value)

      9     

      Continuous recording duration of traveling wave current

      1000μs

      10    

      Communication unit

      communication mode

      All Netcom 4G/5G/WIFI wireless transmission

      11    

      Data security

      VPN dedicated channel can be used for communication with the master station, and encryption transmission is optional.

      12    

      Access protocol

      Access to monitoring platforms of provincial power companies such as Southern Power Grid and State Grid

      13    

      Power supply unit

      Power supply mode

      The normal working current range of induction power supply and solar power supply is 30~1000A;

      14       

      Power supply duration

      The power supply requirement that the device can operate normally for 30 days without continuous illumination.

      15       

      Other parameters

      work environment

      Working temperature: - 40~+70 ℃; Relative humidity: 5-99% RH

      16    

      Overall service life

      More than 8 years

      17    

      Degree of protection

      IP67




      Contact us

      Shenzhen Dinsee Smart Technology Co.,Ltd
      Tel:0755-21612345?Mobile&Whatsapp:+8618926454155
      Fax:0755-21612345Whatsapp:+8618926454155E-Mail:business@szdx.com
      Address: Building 2,xiangyuer Industry Part,NO.8 Longsheng Road,Longgang District,Shenzhen 518126,China

      The online monitoring, distributed fault location and cable online monitoring equipment for power transmission and distribution lines launched by SHENZHEN DINSEE SMART TECHNOLOGY CO.,LTD. has been widely used in Southern Power Grid and State Grid, and has achieved good results.

      Record No.: Yue ICP Bei 2022070794-1 | Website Map XML Map

      主站蜘蛛池模板: 国内精品久久国产大陆| 国产精品久久久久天天影视| 996久久国产精品线观看| 免费观看四虎精品成人| 久久久国产精品福利免费| 正在播放国产精品每日更新 | 久久久久无码国产精品不卡| 一区二区三区精品国产欧美| 99视频精品全部在线观看| 亚洲精品午夜国产VA久久成人| 精品第一国产综合精品蜜芽| 97精品国产高清自在线看超| …久久精品99久久香蕉国产| 日韩精品无码专区免费播放| 香蕉国产精品麻豆亚洲欧美日韩精品自拍欧美v国 | 亚洲精品乱码久久久久久按摩 | 久久精品国产只有精品2020| 亚洲一区二区三区在线观看精品中文| 国产高清精品在线| 国产精品视频分类一区| 国产精品兄妹在线观看麻豆| 亚洲日韩精品无码一区二区三区| 日韩蜜芽精品视频在线观看| 欧美精品一区二区在线精品| 久久乐国产精品亚洲综合 | 久久成人影院精品777| 国产精品亚洲一区二区三区在线 | 国产精品xxxx国产喷水亚洲国产精品无码久久一区 | 国产成人精品视频在放| 国内精品久久久久久99蜜桃| 亚洲高清国产AV拍精品青青草原| 中文字幕日韩精品无码内射| 亚洲性日韩精品国产一区二区| 天天爽夜夜爽夜夜爽精品视频| 欧美 日韩 精品 另类视频| 精品亚洲成α人无码成α在线观看| 国产精品推荐天天看天天爽 | 国产精品免费久久久久久久久| 国产91精品一区二区麻豆亚洲| 成人精品一区二区三区在线观看| 亚洲国产精品国自产电影|